Voltage Stability Evaluation in the Nigeria 44 Bus Grid Network using Modal Analysis

Aneke, E. N. and Ibekwe, B. E. and Iyidobi, J. C. and Okafor, E. N. C. (2021) Voltage Stability Evaluation in the Nigeria 44 Bus Grid Network using Modal Analysis. Journal of Engineering Research and Reports, 20 (11). pp. 80-89. ISSN 2582-2926

[thumbnail of 541-Article Text-862-1-10-20221007.pdf] Text
541-Article Text-862-1-10-20221007.pdf - Published Version

Download (267kB)

Abstract

This paper focused on the application of modal analysis method to determine the voltage stability of the Nigeria 44 bus 330kV transmission grid network and to determine the network’s weakest buses. Modal method calculates the smallest eigenvalue and all the associated eigenvectors of the reduced Jacobian matrix, JR using steady state mode. The network model was developed in PSAT-MATLAB and load flow was performed on the network. Results and analysis showed that the Nigeria 44 Bus grid network was found to be unstable as the modal analysis revealed the presence of eigenvalue with a negative real part. Gombe, Damaturu and Yola buses were also discovered to be the vulnerable buses since their voltage profile fell below the IEEE standard voltage level of (0.95-1.05) pu. Yola bus was spotted as the weakest bus based on the analysis of the participating factors.

Item Type: Article
Subjects: STM Digital > Engineering
Depositing User: Unnamed user with email support@stmdigital.org
Date Deposited: 11 Mar 2023 09:55
Last Modified: 24 Jul 2024 09:58
URI: http://research.asianarticleeprint.com/id/eprint/109

Actions (login required)

View Item
View Item